We previously discussed doing a visual inspection of your distribution system to quickly identify systemic problems

We previously discussed doing a visual inspection of your distribution system to quickly identify systemic problems. However, this approach doesn't identify every likely problem or quantify before/after. For that, you need testing.

If your facility has a power monitor, great. But it's probably not monitoring at every load. To see what's going on at the loads, you need a power analyzer and a true RMS DMM.

Previously, we worked from the one-line down. Now we'll work in the other direction; start at one of the troubled loads.

First, visually inspect for proper separation between wiring of different systems. For example, you don't want 50mV signal wiring run alongside the 480V motor supply.

Next, measure the output of each DC power supply. The voltage should equal nameplate. If not, and the input voltage is correct, then replace the power supply.

Next, measure the power to the cabinet for RMS peak voltage and RMS nominal voltage. You should see about 1.414 times nominal voltage and nominal voltage, respectively.

If either voltage reading is low by 3% or more, go back to your drawings and calculate the conductor sizes for less voltage drop. Although most references say 5% is acceptable, that may be too low when you're trying to run electronics in a high harmonic environment. You're looking at a rewiring project to solve this problem.

In Part 6, we'll look at some other testing to perform.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...