AC or DC General-Use Snap Switches

March 28, 2014
Snap switches shall be used as noted in Section 404.14(A) through (F) of the 2011 NEC.

AC or DC general-use snap switches may be used for control of inductive loads not exceeding _____% of the ampere rating of the switch at the applied voltage.

a) 50
b) 75
c) 90
d) 100

See answer and applicable Code reference

The correct answer is: a) 50%

Snap switches shall be used as noted in Section 404.14(A) through (F) of the 2011 NEC. As noted in 404.14(B)(2), the use of general use snap switches suitable for use on AC or DC circuits for controlling inductive loads shall not exceed 50% of the ampere rating of the switch at the applied voltage. Switches rated in horsepower are suitable for controlling motor loads within their rating at the voltage applied.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...