Raceway Restrictions in a Pull Box

May 5, 2014
The rules for pull and junction boxes, as well as conduit bodies, are outlined in Sec. 314.28 of the 2011 NEC.

Where angle or U pulls are made, the distance between each raceway entry inside the box or conduit body and the opposite wall of the box or conduit body shall not be less than _____ times the trade size of the largest raceway in a row plus the sum of the trade sizes of the remaining raceways in the same wall and row.

a) six
b) eight
c) ten
d) twelve

See answer and applicable Code reference

The correct answer is: a) six

The rules for pull and junction boxes, as well as conduit bodies, are outlined in Sec. 314.28 of the 2011 NEC. As noted in the first sentence of 314.28(A)(2), "Where splices or where angle or U pulls are made, the distance betwwen each raceway entry inside the box or conduit body and the opposite wall of the box or conduit body shall not be less than six times the metric designator (trade size) of the largest raceway in a row."

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Strut Corrosion Guide

Learn how Champion Strut™ benefits projects with corrosion resistance.