Does your facility have any areas used for spraying, dipping, or coating processes? If these operations run regularly, you must apply Art. 516 [516.1].

Does your facility have any areas used for spraying, dipping, or coating processes? If these operations run regularly, you must apply Art. 516 [516.1].

Article 516 differentiates between a spray room, spray booth, and spray area [516.2]:

  • Spray room: A dedicated room with dedicated ventilation supply and exhaust.
  • Spray booth: A dedicated enclosure (within a room) with dedicated ventilation exhaust (ventilation supply needn’t be dedicated).
  • Spray area: An area that has some local vapor extraction or ventilation.

Some requirements apply to only one or two of the above. Regardless of whether you have a room, booth, or enclosure, you must classify the location [516.3]. The location must conform to the applicable requirements that follow from 516.5 onward.

Classification isn’t as hard as it sounds:

  • The interior of a container of flammable liquid is Class I, Division 1 or Class I, Zone 0.
  • The interiors of spray booths, exhaust ducts, sumps, and some other areas are Class I or Class II, Division 1.
  • Places open to air are generally Class I or Class II, Division 2.
Use Figure 516.3(C)(5) to help you determine with which classification you are working.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.