Separately Derived System

Aug. 1, 2001
How you ground a separately derived system is critical to the safety of those working on the system and the performance of your equipment. Separately derived systems are power sources with no direct electrical connection between any of the circuit conductors and supply conductors. For example, no direct connection exists between the primary and secondary winding of a delta-wye transformer. Generators,

How you ground a separately derived system is critical to the safety of those working on the system and the performance of your equipment.

Separately derived systems are power sources with no direct electrical connection between any of the circuit conductors and supply conductors. For example, no direct connection exists between the primary and secondary winding of a delta-wye transformer. Generators, converter windings, UPS systems, and solar photovoltaic systems are separately derived systems only when all circuit conductors — including the grounded (neutral) conductor — are independent of the supply conductors. If you wish to use a separately derived system, you must use a 3-pole transfer switch for a single-phase, 3-wire system, or a 4-pole transfer switch for a 3-phase, 4-wire system [Art. 100 definition and Sec. 250-20(d) FPN No.1].

The National Electrical Code (NEC) has several rules that contain specific requirements for grounding separately derived systems. Failure to properly ground separately derived systems can result in electric shock, electrocution, fire, equipment failure, and poor power quality.

Electric shock [Sec. 250-104(a)(4)]

To prevent a hazardous voltage difference between metal water piping systems and metal electrical equipment caused by faults or voltage transients, you must bond metallic water pipe systems in the area served by the separately derived system to the grounded (neutral) conductor of the separately derived system.

Electrocution [Secs. 250-2(d), 250-20(d), and 250-30]

Installing a separately derived system and not grounding it properly can create a dangerous condition where a phase-to-case fault cannot be removed. As a result, all metal parts of the electrical system — as well as the building structure — will remain energized with line voltage if a phase-to-ground fault occurs.

Fire hazard and electric shock [Secs. 250-6 and 250-142]

Improper neutral-to-case connections at separately derived systems create multiple neutral-to-case connections. This allows neutral current to have multiple return paths to the grounded (neutral) conductor of the power supply. Improper neutral-to-case connections can create objectionable current flow on metal parts, resulting in a fire and/or shock hazard.

Equipment failure [Secs. 250-2(a), 250-20(d), and 250-242]

You must ground a separately derived system to the earth per the NEC to stabilize the phase-to-case voltage [Sec. 250-2(a)]. According to the IEEE Std. 242 (the Buff Book), Sec. 7.2.5, an improperly grounded system could be subjected to severe overvoltage to ground — as high as six or eight times phase voltage. This can puncture insulation and result in additional ground faults. Repetitive charging of the system capacitance, or resonance between the system capacitance and the inductances of system equipment can cause these overvoltages.

Power quality. [Secs. 250-6 and 250-142]

Improper neutral-to-case connections can elevate case-to-earth voltage, which leads to power quality problems, and create neutral current flow on metal parts of the electrical system, causing electromagnetic interference.

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...