Code Quiz

March 8, 2005
A general power and lighting feeder tap that consists of 1/0 AWG THHN conductors has been made to 500 kmcil THHN feeder conductors in a properly sized junction box. The 500 kcmil feeder conductors are protected by a 400A OCPD at the point where they ...

A general power and lighting feeder tap that consists of 1/0 AWG THHN conductors has been made to 500 kmcil THHN feeder conductors in a properly sized junction box. The 500 kcmil feeder conductors are protected by a 400A OCPD at the point where they receive their supply. The 1/0 AWG feeder tap conductors are protected at their termination point by a 150A overcurrent device. The feeder equipment grounding that runs with the 500 kcmil feeders is 3 AWG. What's the minimum size equipment grounding conductor required as part of the feeder tap circuit conductors?

A) 8 AWG
B) 6 AWG
C) 3 AWG
D) 1/0 AWG

Answer: C)

Explanation: Per a 2005 change, 250.122(G) requires that when sizing equipment grounding conductors for feeder taps, the minimum size of the equipment grounding conductor to be installed with the feeder tap conductors shall be based on the rating of the overcurrent device protecting the feeder conductors.

A feeder protected by a 400A OCPD requires a 3 AWG equipment grounding conductor. According to this change, the feeder tap conductor would also have to be a 3 AWG equipment grounding conductor.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.