Code Quiz

April 22, 2005
Consider the following situation: Three black 12 AWG THHN conductors pass directly through a box, uncut and unspliced. Three red 12 AWG THHN conductors are looped in the box. The loop measures 12 inches for each conductor. Six white (grounded) ...

Consider the following situation: Three black 12 AWG THHN conductors pass directly through a box, uncut and unspliced. Three red 12 AWG THHN conductors are looped in the box. The loop measures 12 inches for each conductor. Six white (grounded) conductors are also looped with 12-inch loops. As would be expected, a green 12 AWG equipment grounding conductor originates at the panelboard and is installed with the branch-circuit conductors, cut into two pieces (each measuring 6 inches) within the box. An equipment bonding jumper is also pigtailed within the box (to the equipment grounding conductors), bonding the equipment grounding conductors to the box, but it doesn’t leave the box. What’s the minimum cubic inch capacity for the box?

A) 29.25 cu. in.
B) 31.50 cu. in.
C) 33.75 cu. in.
D) 49.50 cu. in.

Answer: D)

Per a 2005 NEC change, 314.16(B)(1) was revised to address looping of conductors within boxes. If the looped conductor measures 12 inches or more on its exposed length within the box, with reference to section 300.14, each looped conductor will now be considered to be two conductors. As has been the case for some time, a conductor that passes through the box, uncut, unspliced, and not looped 12 inches or more counts as only one conductor. Any conductor that is cut is counted as two conductors. One or more equipment grounding conductors count only as one conductor.

To find the mimimum size in cubic inches of a box for this application, you have to perform the following calculations:

Three black 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 3 = 6.75 cu. in. (uncut, unspliced)

Three red 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 3 X 2 = 13.5 cu. in. (because of the loop)

Six white 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
6 X 2.25 X 2 = 27 cu. in. (because of the loop)

Two green 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 1 = 2.25 cu. in. (because equipment grounding conductors count only as one)

One green 12 AWG THHN pigtail equipment bonding conductor, which originates in the box and doesn’t leave the box does not count.

Minimum box size:
6.75 + 13.5 + 27 + 2.25 = 49.5 cu. in.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Xpress Elbows Guide for Industrial Construction

Learn how to get expedited elbows shipped within 2 days.