Code Q&A: Ground Rod Electrodes

Nov. 21, 2013
Your most pressing National Electrical Code (NEC) questions answered

Q. What are the requirements related to the use of a ground rod for the grounding electrode system, including sizing of the grounding electrode conductor? (Answer based on 2011 NEC.)

A. Ground rod electrodes must not be less than 8 ft in length in contact with the earth [250.53(G)]. Rod-type electrodes must have a diameter of at least 5/8 in., unless listed [250.52(A)(5)(b)]. Rod, pipe, or plate electrodes must meet the following requirements [250.53(A)]:

1) If practicable, rod, pipe, and plate electrodes must be embedded below the permanent moisture level and be free from nonconductive coatings such as paint or enamel.

2) A single rod, pipe or plate electrode must be supplemented by an additional electrode that’s bonded to one of the following:

  • The single rod, pipe, or plate electrode
  • The grounding electrode conductor of the single electrode
  • The neutral service-entrance conductor
  • The nonflexible grounded service raceway
  • The service enclosure

Exception: If a single rod, pipe, or plate grounding electrode has an earth contact resistance of 25 ohms or less, the supplemental electrode isn’t required.

The grounding electrode conductor, if it’s the sole connection to the ground rod, isn’t required to be larger than 6 AWG copper [250.66(A)]. In addition, the diameter of a ground rod has an insignificant effect on the contact resistance of a ground rod to the earth. However, larger diameter ground rods (¾ in. and 1 in.) are sometimes installed where mechanical strength is desired, or to compensate for the loss of the electrode’s metal due to corrosion.

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Xpress Elbows Guide for Industrial Construction

Learn how to get expedited elbows shipped within 2 days.