Ecmweb 3157 807ewcqfig1

Stumped by the Code?

Aug. 14, 2008
Am I required to secure Type MC cable that is located under a raised floor of an information technology equipment room?

Q. Am I required to secure Type MC cable that is located under a raised floor of an information technology equipment room?

A. Yes. All wiring methods under raised floors must be secured in accordance with the wiring method requirements [645.5(D)(2)]. For example, Type MC cable with four or less conductors sized no larger than 10 AWG must be secured within 12 inches of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 6 feet [330.30].

If the room is compliant with 645.4 and the power cables (MC) are listed as part of, or for, information technology equipment, they are not required to be secured in place per 645.5(E)

Q. How many receptacles can be installed on a generalpurpose branch circuit?

A. The NEC doesn't limit the number of receptacle outlets on a generalpurpose branch circuit in a dwelling unit [220.14(J)], but for other than dwelling units, the NEC limit is 13 receptacle outlets each at 180VA per mounting strap [220.14(I).

Circuit VA = Volts × Amperes

Circuit VA = 120V × 20A = 2,400VA

Number of receptacles = 2,400VA ÷ 180VA = 13

According to the NEC Handbook published by the NFPA, receptacle loads are not considered a continuous load; therefore, the calculation is based on 20A, not 80% of 20A.

Q. How many 12 AWG conductors can I install in a 1inch EMT raceway?

A. EMT must be large enough to permit the installation and removal of conductors without damaging the conductor insulation [358.22]. This is accomplished by complying with conductor fill limitations of Table 1 of Chapter 9. Because all of the conductors are the same size, Annex C, Table C.1 can be used to determine the number of conductors (26 conductors).

Although the NEC permits 26 12 THHN conductors in trade size 1 EMT, 310.15(B)(2)(a) requires the ampacity of the conductors to be adjusted when installing more than three currentcarrying conductors in the raceway.

Q. What are the NEC requirements when using Type MC or NM cable as the feed and switchleg for a singlepole switch?

A. The white conductor within the cable must be used to supply the power to the switch, and it must be permanently reidentified at each location where the conductor is visible to indicate its use as an ungrounded conductor [200.7(C)(2)]. The black conductor is to be used as the switch leg to the luminaire.

Q. What are the rules for terminating more than one conductor on a terminal?

A. The general requirement is that all terminals are rated for the termination of only one conductor. Terminals suitable for more than one conductor must be identified for this purpose, either within the equipment instructions or on the terminal itself [110.14(A)]. Some circuit breakers that are rated 30A or less are listed for the termination of two conductors, and this information is contained in the product instructions.

Q. What are working space requirements for telecommunications equipment?

A. The working space requirement for power equipment contained in 110.26(A) does not apply to communications equipment [90.3]; however, the telecommunications equipment cannot be located in the required workspace for power equipment.

Q. Can a receptacle for a LCD projector that is cordandplugconnected be located above a suspended ceiling?

A. No. Cords are not permitted to be run through holes in structural or suspended/dropped ceilings [400.8(2)]. They are also not allowed to be concealed by walls, floors, or ceilings, or located above suspended or dropped ceilings [400.8(5)].

Q. What are the cable fill limitations when installing telecom cable in a raceway?

A. Where communications cables are installed in a Chapter 3 raceway, the raceway must be installed in accordance with Chapter 3. The raceway fill requirements of Chapter 3 and Chapter 9 do not apply [800.110].

Q. Is a disconnect required to be within sight of electric spaceheating equipment if the unit has a factoryinstalled circuit breaker?

A. No. A unit switch with a marked “off” position that is an integral part of the equipment can serve as the heater disconnecting means, if it disconnects all ungrounded conductors of the circuit [424.19(C)].

Q. What are the GFCI protection requirements for 15A and 20A, 125V receptacles?

A. GFCI protection is required for all 15A and 20A, 125V receptacles located in:

(A) Dwelling Units [210.8]:

  • Bathroom area

    GFCI protection is required for all 15A and 20A, 125V receptacles in the bathroom area of a dwelling unit.

  • Garages and accessory buildings

    GFCI protection is required for all 15A and 20A, 125V receptacles in garages, and in gradelevel portions of accessory buildings used for storage or work areas of a dwelling unit.

  • Outdoors

    All 15A and 20A, 125V receptacles located outdoors of dwelling units, including receptacles installed under the eaves of roofs, must be GFCI protected.

    Exception to (3): GFCI protection isn't required for a fixed electric snowmelting or deicing equipment receptacle supplied by a dedicated branch circuit, if the receptacle isn't readily accessible and the equipment or receptacle has groundfault protection of equipment (GFPE) [426.28].

  • Crawl spaces

    All 15A and 20A, 125V receptacles installed in crawl spaces at or below grade of a dwelling unit must be GFCI protected.

  • Unfinished basements

    GFCI protection is required for all 15A and 20A, 125V receptacles located in the unfinished portion of a basement not intended as a habitable room and limited to storage and work areas.

    Exception to (5): A receptacle supplying only a permanently installed fire alarm or burglar alarm system is not required to be GFCI protected [760.41(B) and 760.121(B)].

  • Kitchen countertop surfaces

    GFCI protection is required for all 15A and 20A, 125V receptacles that serve countertop surfaces in a dwelling unit.

  • Laundry, utility, and wet bar sinks

    GFCI protection is required for all 15A and 20A, 125V receptacles located within an arc measurement of 6 ft from the sink.

  • Boathouses

    GFCI protection is required for all 15A and 20A, 125V receptacles located in a dwelling unit boathouse.

(B) Other than dwelling units [210.8]. GFCI protection is required for all 15A and 20A, 125V receptacles installed in the following nondwelling locations:

  • Bathrooms

    All 15A and 20A, 125V receptacles installed in commercial or industrial bathrooms must be GFCI protected.

  • Kitchens

    All 15A and 20A, 125V receptacles installed in an area with a sink and permanent facilities for food preparation and cooking [Art. 100], even those that don't supply the countertop surface, must be GFCI protected.

  • Rooftops

    All 15A and 20A, 125V receptacles installed on rooftops must be GFCI protected.

  • Outdoors

    All 15A and 20A, 125V receptacles installed outdoors must be GFCI protected.

    Exception No. 1 to (3) and (4): GFCI protection isn't required for a fixed electric snowmelting or deicing equipment receptacle supplied by a dedicated branch circuit, if the receptacle isn't readily accessible and the equipment or receptacle has groundfault protection of equipment (GFPE) [426.28].

  • Sinks

    All 15A and 20A, 125V receptacles installed within 6 feet of the outside edge of a sink must be GFCI protected.

Additional GFCI protection requirements are required for:

  • Receptacle replacement 406.3(D)(3)

  • Luminaire replacement 410.42(B) Exception

  • Vending machines 422.51

  • Repair garages 511.12

  • Aircraft hangers 513.12

  • Carnivals, circuses, and fairs 525.23

  • Agricultural building 547.5(G)

  • Boatyards 555.19(B)

  • Temporary wiring 590.6

  • Elevators and machine rooms 620.85

  • Pools, spas and hot tubs, fountains, and hydromassage bathtubs Art. 680.

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.