When installing a concealable nonmetallic extension from an existing 15A non-grounding receptacle outlet in an existing dwelling unit

Q. When installing a concealable nonmetallic extension from an existing 15A non-grounding receptacle outlet in an existing dwelling unit, where there is no equipment grounding conductor, is it permissible to install grounding-type receptacles as part of the nonmetallic extension?

  1. Under no condition is a grounding-type receptacle permitted, as there is no equipment grounding conductor or grounding provision in the existing circuit.
  2. Yes, if an AFCI receptacle is installed to protect all receptacle outlets on the branch circuit.
  3. Yes, however, the only method permitted is the use of GFCI receptacles.
  4. Yes, if grounded in accordance with 250.130(C), 406.3(D)(3)(b), or 406.3(D)(3)(c).

Answer: D

Where a concealable nonmetallic extension originates from a non-grounding-type receptacle, the installation shall comply with 250.130(C), 406.3(D)(3)(b), or 406.3(D)(3)(c). There are three choices. Two of the three require GFCI protection; 406.3(D)(3)(b) and 406.3(D)(3)(c). See 382.10(A).

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...