Code Quiz

Feb. 7, 2008
On a 3-phase, 4-wire, 480/277V service, a question has arisen as to the required rating of the service disconnect. The calculated load is 780A. The fusible disconnecting means is rated at 1,000A, based on the maximum fuse size that can be installed.

Q. On a 3-phase, 4-wire, 480/277V service, a question has arisen as to the required rating of the service disconnect. The calculated load is 780A. The fusible disconnecting means is rated at 1,000A, based on the maximum fuse size that can be installed. What is the minimum rating of the service disconnect permitted for this application?

  1. 800A
  2. 900A
  3. 1,000A
  4. All of the above

Answer: C

As per the second paragraph of 230.95, “The rating of the service disconnect shall be considered to be the rating of the largest fuse that can be installed or the highest continuous current trip setting for which the actual overcurrent device installed in a circuit breaker is rated or can be adjusted.”

The calculated value in this example would have permitted an 800A rated disconnecting means, however, because of the possibility of a 1,000A rated fuse being installed in this disconnect, the rating of this disconnect shall be a minimum of 1,000A.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.