Code Quiz

Oct. 21, 2010
When enclosing electrical equipment in an outdoor installation, other than equipment as described in 110.31(D), what is the minimum distance required between the fence and the live parts when the nominal voltage is 34.5kV?

When enclosing electrical equipment in an outdoor installation, other than equipment as described in 110.31(D), what is the minimum distance required between the fence and the live parts when the nominal voltage is 34.5kV?

  1. 3.05 m
  2. 5.49 m
  3. 18 ft
  4. 15 ft

Answer: D

The rules for this type of installation are found in Article 110. More specifically, as noted in Table 110.31 (Minimum Distance From Fence to Live Parts) the distance from the fence to the live parts shall not be less than 15 ft.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...