Code Quiz

April 7, 2011
What is the minimum size grounded conductor required for the following installation?

What is the minimum size grounded conductor required for the following installation?

A service consists of a NEMA 3R service-rated fusible disconnect. The load supplied is a 100 hp, 460V, 3-phase motor for a pump in the middle of a field (with appropriate motor controls and equipment). The ungrounded service entrance conductors are 2/0 AWG XHHW. The electric utility supplied service is 3-phase, 4-wire grounded.

  1. 1/0 XHHW (70% of 2/0)
  2. 2/0 XHHW
  3. No. 1 XHHW (2 sizes smaller than 2/0)
  4. No need for a grounded conductor since the motor is 3-phase.

Answer: B

Because the electric utility service is grounded, a grounded conductor must be installed. As noted in 250.24(C)(3), the grounded conductor shall have an ampacity not less than that of the ungrounded conductors. This is a new requirement in the 2011 edition of the NEC.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Latest from Quizzes

Photo 53038280 © Wenling01 | Dreamstime.com
Photo 312186162 © Cagkan Sayin | Dreamstime.com
Photo 311647339 © Andrei Dodonov | Dreamstime.com