Code Quiz

Jan. 22, 2009
At an agricultural (farm) site, which one of the following locations does not require ground-fault circuit-interrupter protection for all 125V, single-phase, 15A and 20A general-purpose receptacles?

At an agricultural (farm) site, which one of the following locations does not require ground-fault circuit-interrupter protection for all 125V, single-phase, 15A and 20A general-purpose receptacles?

  1. an accessible receptacle supplying a dedicated load where a GFCI protected receptacle is located within 3 ft of the non-GFCI protected receptacle
  2. areas having an equipotential plane
  3. outdoors
  4. damp or wet locations
  5. dirt confinement areas for livestock

Answer: A

New text at the end of 547.5(G) reads like an exception to the GFCI-protection requirements in agricultural buildings noted in (1) through (4). Dedicated loads include equipment like brooders and incubators, as well as feed mixers, conveyors, and grinders.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...