• Code Quiz: Horizontal Support Requirements for Cable Routing Assemblies

    NEC guidelines for installing horizontal supports for cable routing assemblies
    March 12, 2015

    Fill in the blank with the appropriate answer.

    When installing communication wires and cables in cable routing assemblies, horizontal supports for cable routing assemblies shall be installed at intervals not to exceed _____ at each end or joint unless listed otherwise. In no case shall the distance between supports exceed _____.

    A)  3 ft/6 ft

    B)  3 ft/10 ft

    C)  4½ ft/8 ft

    D)  5 ft/10 ft

    Find the Answer

    Answer: B

    As per Sec. 800.110(C)(1) of the 2014 NEC, when installing communication wires and cables in cable routing assemblies, horizontal supports shall be installed at intervals not to exceed 3 ft at each end or joint unless listed otherwise. In no case shall the distance between supports exceed 10 ft.