NEC Rules on Motor Controller Grounding Requirements, controller enclosures

Excluding exceptions, motor controller enclosures shall be connected to the equipment grounding conductor (EGC) ______________. Controllers shall have a means for attachment of an EGC termination in accordance with ____________.

A) Every time / the manufacturer’s instructions
B) Only for grounded systems / the engineer’s specifications
C) Only for ungrounded systems / NEC Sec. 250.66
D) Regardless of the voltage / NEC Sec. 250.8

Scroll Down to See Answer 

Answer: D

Article 430 of the 2017 NEC focuses on motors, motor circuits and controllers. Part XIII of this Article covers the grounding requirements for all voltages. As per Sec. 430.244 (excluding the exception), “Controller enclosures shall be connected to the equipment grounding conductor regardless of the voltage. Controller enclosures shall have a means for attachment for an equipment grounding conductor termination in accordance with 250.8.”

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Xpress Elbows Guide for Industrial Construction

Learn how to get expedited elbows shipped within 2 days.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...