Illustrated Catastrophes

June 1, 2006
As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions. All references are based on the 2005 NEC. TAKING PERFECT AIM Karl Darby, owner, Darby Electrical, Stockton, N.J., found this installation at his new

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2005 NEC.

Taking Perfect Aim. Karl Darby, owner, Darby Electrical, Stockton, N.J., found this installation at his new next door neighbor's house. “Once the house was finished, and we headed over to meet the new neighbors, I spotted the electric service. As you can see, it appears the cable TV installer drilled a hole from the cellar, out through the siding, and right through the service lateral conduit, apparently without hitting an energized conductor. Amazing! The best part is they neatly caulked the penetration after installing their coax. Also note the grounding wire is disconnected.”This work shows a clear lack of proper training, which could have easily resulted in a fatality. This installer was most likely unaware of what could have happened to him if the drill penetrated the energized conductor. Lucky for him, it probably penetrated the grounded (neutral) conductor. The NEC doesn't list a specific rule for disconnecting the lateral with service entrance conductors in it.

Burning Down the House. David J. Delany, P.E., senior electrical engineer, FreemanWhite, Inc., Raleigh, N.C., ran across this arrangement in a friend's 20-year-old house. “I found it like this when I removed the panel cover to install a new breaker for him. I don't have a picture of the meter socket, but it was just as burnt up. It looks like a few things caused this problem. The panel is located in a utility room attached to the house. The room is accessed via an outside door, which is left open at times, allowing damp conditions at the panel. Combine this with aluminum conductors and loose connections and the result is overheated conductors. Luckily, the house didn't burn down before the equipment was replaced.”

Remember to torque those connections as required by the instructions on the panel, and watch out for those long trim screws. The screw on the right top originally penetrated the hot phase conductor and helped cause this damage because of the missing main bonding jumper.

Found a Code Violation? E-mail your photos to Joe Tedesco at [email protected].

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.