Illustrated Catastrophes

Aug. 1, 2004
As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions. BEWARE WHAT LURKS IN THE CRAWL SPACE Patrick Dacey, NACHI member, SouthWest Inspections, recently sent me these photos of this interesting arrangement

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.



BEWARE WHAT LURKS IN THE CRAWL SPACE

Patrick Dacey, NACHI member, SouthWest Inspections, recently sent me these photos of this interesting arrangement that he took during a mobile home inspection in June. Both wiring arrangements are located within the crawl space of a doublewide mobile home. The outlet and box were found directly below the water heater and the “web of wires” was located below the two halves of the trailer.

These wiring arrangements violate the requirements of Chapter 3 and 550.3, which states, “Wherever the requirements of other articles of this Code and Article 550 differ, the requirements of Article 550 shall apply.”











WHY IS MY ELECTRIC BILL SO HIGH?

Thomas Erfert, a Code enforcement specialist from Yuma, Ariz., has been investigating the theft of electricity for many years. He recently ran across this installation and decided to share the story with us.

A mobile home power-supply cord must be a listed type with four conductors, one of which is required to be identified by a continuous green color or a continuous green color with one or more yellow stripes for use as the equipment grounding conductor. This cord must be permanently attached to the distribution panelboard or to a junction box that's permanently connected to the distribution panelboard. A suitable clamp or the equivalent must also be provided at the distribution panelboard knockout to afford strain relief for the cord. This prevents strain from being transmitted to the terminals when the power-supply cord is handled in its intended manner. The free end is required to terminate in an attachment plug cap.

This installation seems to meet these requirements, but there's also evidence that someone is stealing electricity. The individual appears to be using the bare ends of a cord, which were cut to expose the wires that are positioned to receive energy from the once legally connected attachment plug cap. Any cords with adapters and pigtail ends, extension cords, and similar items can't be attached to, or shipped with, a mobile home. See the requirements of 550.10(B) for power-supply cords.



DISCONNECT SWITCH PLAYS HIDE AND SEEK

David Fredericks, electrical engineer, Chu and Gassman Consulting Engineers, Middlesex, N.J., found this in a storage room while surveying the service entrance equipment for a train station in New York. Fredericks noted that this disconnect switch serves as the main service disconnect for a small concession stand at the station.

As we've seen many times before, this is a violation of the requirements of 110.26(B), which states, “Working space required by this section shall not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, shall be suitably guarded.”

Found a Code violation? E-mail your photos to Joe Tedesco at [email protected].

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.