What's Wrong Here?

July 22, 2005
Hint: Don’t focus on the wiring this time

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.

Find the Answer

Answer:

I found this junction box in a basement located directly under a street near the U.S. Capitol. It was being removed due to severe corrosion caused by salt water. No, it wasn’t near the oceans edge, but below an area where street salt runoff collected during the winter months of the year. This wasn’t the fault of the equipment manufacturer or the installer, but rather the fault of the property owner who choose not to make the necessary repairs to stop the leaks.

Art. 314, Part III, of the 2005 NEC covers the installation and use of all boxes and conduit bodies used as an outlet, device, junction, or pull box, depending on its use, and handhole enclosures. The requirements in 314.40(A) call for metal boxes, conduit bodies, and fittings to be corrosion resistant or well galvanized, enameled, or otherwise properly coated inside and out to prevent corrosion. A Fine Print Note directs you to 300.6 for limitation in the use of boxes and fittings protected from corrosion solely by enamel.

For a close-up of this picture, click here.

> Try Another Quiz

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.