Ecmweb 4870 305ecm15pic1

What's Wrong Here?

May 1, 2003
Hint: This flexible cord assembly supplies temporary stage equipment in the ballroom of a major New Orleans hotel.

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.

Find the Answer

The following individuals correctly identified the Code violations shown in the May column: Travis Halstead, general foreman, Morrow Meadows Corp., City of Industry, Calif.; John Lundberg, engineer, Cupertino Electric, Santa Clara, Calif.; Richard Erle, electric foreman, Florida Hospital, Altamonte Springs, Fla.

The flexible cord used in this installation was connected with a fitting that wasn't designed for this purpose. And even if it was designed specifically for this cord, it still can't be used for the permanent supply to stage equipment. Flexible cords can't be used as a substitute for fixed wiring under any circumstances (400.8).

In addition, the metallic cable assembly that runs from the cabinet to the device box enclosing the receptacle isn't properly secured, and the fitting that was used may not be designed for this use. Per 110.3(B), listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.

See Art. 320 and Art. 330 for specific support requirements for these types of wiring methods. See 320.30 for securing and supporting Type AC Cable and 330.30 for securing and supporting Type MC cable.

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Strut Corrosion Guide

Learn how Champion Strut™ benefits projects with corrosion resistance.