The Code does not specify which method of identification must be used for any particular voltage class or system type.

All references are based on the 2017 edition of the NEC, unless otherwise noted.

Each of the conductors shown in the Photo could be used as a grounded conductor in accordance with Sec. 200.6(A). Perhaps the white wire could be used for the neutral of a 120/240V system while the white wire with the red tracer used as the grounded conductor of a corner-grounded delta system.

The Code does not specify which method of identification must be used for any particular voltage class or system type. It’s the installer’s choice. In fact, if conductors for these systems are kept in raceways and enclosures, separate from the other systems, the installer could choose to use only one of these identification methods for any and all grounded conductors. For example, white insulation could be used for all grounded conductors. However, if any of the grounded conductors from other systems are installed in the same raceway or enclosure, using only one color such as the white would be a violation of Sec. 200.6(D).

But what if all the voltages are the same? For instance, what if there are several 208Y/120V panels being powered from different transformers installed in the electric room, with the 120V branch circuits from one panel installed in the same wireway with 120V branch circuits from the other panels? In this case, would each grounded conductor in the wireway need to be identified differently than the grounded conductors coming from the other panels?

The literal wording in Sec. 200.6(D) appears to require the grounded branch-circuit conductors coming from each 208Y/120V panel to be identified differently than the other grounded conductors in the same wireway. The voltage and type of systems may all be the same, but these circuits are, in fact, being fed from different separately derived systems. Using white insulation to identify each grounded conductor in this case literally would be a violation of Sec. 200.6(D) because it states “different systems” rather than “different types of systems” or “different nominal voltage systems” in the way Sec. 210.5(C)(1) does for ungrounded conductors. Application of the rule in this way may not be the intent, but there are many other types of “systems” throughout the Code, including optional standby, legally required, energy storage, and energy management, among others, that may need to comply with Sec. 200.6(D) as well.

It would be best to have a conversation your authority having jurisdiction (AHJ) about how to properly identify any grounded conductors.

About the Author

Russ LeBlanc | Owner

Russ started in the electrical trade as an apprentice in 1985. He worked his way up to become a Journeyman Electrician and then eventually became a Master Electrician and Licensed Construction Supervisor. In 1999 Russ become an Electrical Instructor for The Peterson School of Engineering in Massachusetts where he developed his passion for teaching, and quickly became Department Head of Electrical Instruction. Russ has taught thousands of apprentices, electricians, engineers, inspectors, and other electrical professionals during his career as an instructor. He continues to provide electrical professionals with Electrical Code seminars, Arc-Flash Awareness training seminars and educational material through his LeBlanc Consulting Services in North Reading, MA whose specialty is educating electricians. He has been an active member of the NFPA Electrical Section and has authored hundreds of National Electrical Code proposals and comments which have become Code rules to improve the safety for the electrical industry. Russ is also an IAEI certified Electrical Inspector.

Please visit www.russleblanc.net for more information.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...