Stumped by the Code? NEC Requirements for Sizing Boxes for Conductor Fill

Feb. 18, 2016
Your most pressing National Electrical Code (NEC) questions answered

All questions and answers are based on the 2014 NEC.

Q. What are the NEC requirements for sizing boxes for conductor fill?

A. Boxes containing 6 AWG and smaller conductors must be sized in an approved manner to provide free space for all conductors, devices, and fittings. In no case can the volume of the box, as calculated in Sec. 314.16(A), be less than the volume requirement as calculated in Sec. 314.16(B) [314.16]. Conduit bodies must be sized in accordance with Sec. 314.16(C).

Pay attention to the length of the loop when determining the number of conductors.

Note: The requirements for sizing boxes and conduit bodies containing conductors 4 AWG and larger are contained in Sec. 314.28. The requirements for sizing handhole enclosures are contained in Sec. 314.30(A).

Box volume calculations — the volume of a box includes the total volume of its assembled parts, including plaster rings, extension rings, and domed covers that are either marked with their volume in cubic inches or are made from boxes listed in Table 314.16(A).

Box fill calculations — The calculated conductor volume determined by Sec. 314.16(B)(1) through (5) and Table 314.16(B) are added together to determine the total volume of the conductors (see Table below), devices, and fittings. Raceway and cable fittings, including locknuts and bushings, aren’t counted for box fill calculations.

Use this handy table when performing your box fill calculations.

Conductor volume — Each unbroken conductor that runs through a box (and each conductor that terminates in a box) is counted as a single conductor volume in accordance with Table 314.16(B). Each loop or coil of unbroken conductor having a length of at least twice the minimum length required for free conductors in Sec. 300.14 must be counted as two conductor volumes. Conductors that originate and terminate within the box, such as pigtails, aren’t counted at all (Figure).

Note: According to Sec. 300.14, at least 6 in. of free conductor, measured from the point in the box where the conductors enter the enclosure, must be left at each outlet, junction, and switch point for splices or terminations of luminaires or devices.

An Exception in this Section notes that equipment grounding conductors, and up to four 16 AWG and smaller fixture wires, can be omitted from box fill calculations if they enter the box from a domed luminaire or similar canopy, such as a ceiling paddle fan canopy.

Cable clamp volume — One or more internal cable clamps count as a single conductor volume in accordance with Table 314.16(B), based on the largest conductor that enters the box. Cable connectors that have their clamping mechanism outside of the box aren’t counted.

Support fitting volume — Each luminaire stud or luminaire hickey counts as a single conductor volume in accordance with Table 314.16(B), based on the largest conductor that enters the box. Note: Luminaire stems don’t need to be counted as a conductor volume.

Device yoke volume — Each single-gang device yoke (regardless of the ampere rating of the device) counts as two conductor volumes, based on the largest conductor that terminates on the device in accordance with Table 314.16(B). Each multi-gang device yoke counts as two conductor volumes for each gang, based on the largest conductor that terminates on the device in accordance with Table 314.16(B).

Equipment grounding conductor volume — All equipment grounding conductors in a box count as a single conductor volume in accordance with Table 314.16(B), based on the largest equipment grounding conductor that enters the box. Insulated equipment grounding conductors for receptacles having insulated grounding terminals (isolated ground receptacles) [250.146(D)] count as a single conductor volume in accordance with Table 314.16(B). Note: Conductor insulation isn’t a factor that’s considered when determining box volume calculations.

This example problem helps explain these concepts in a practical application:

How many 14 AWG conductors can be pulled through a 4-in.-square × 2½-in.-deep box with a plaster ring with a marking of 3.60 cu. in.? The box contains two receptacles, five 12 AWG conductors, and two 12 AWG equipment grounding conductors.

Step 1: First, determine the volume of the box assembly [314.16(A)] as follows:

Box 30.30 cu. in. + 3.60 cu. in. plaster ring = 33.90 cu. in.

A 4 × 4 × 21/8 in. box has an interior volume is 30.30 cu. in., as listed in Table 314.16(A). Note: The gross volume of a box based on Table 314.16(A) dimension (4 in. × 4 in. × 21/8 in. = 34 cu. in.) doesn’t take into account the actual volume of the material used to make the box. This is why the interior volumes on this table are smaller than the overall volumes.

Step 2: Next, determine the volume of the devices and conductors in the box:

Two – receptacles = 4 – 12 AWG conductors

Five – 12 AWG conductors = 5 – 12 AWG conductors

Two – 12 AWG ground conductors = 1 – 12 AWG conductor

This equates to a total of ten 12 AWG conductors: 10 × 2.25 cu in. = 22.50 cu in.

Step 3: Determine the remaining volume permitted for the 14 AWG conductors:

33.90 cu in. – 22.50 cu in. = 11.40 cu in.

Step 4: Determine the number of 14 AWG conductors permitted in the remaining volume:

14 AWG = 2.00 cu in. each [Table 314.16(B)]

11.40 cu in. ÷ 2.00 cu in. = 5 conductors 

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.