Excluding any exception(s), what is the minimum ampacity of the conductors from the generator terminals to first distribution device containing overcurrent protection?
A. Not less than 100% of the nameplate current rating of the generator.
B. Not less than 115% of the nameplate current rating of the generator.
C. Not less than 125% of the nameplate current rating of the generator.
D. Not less than 135% of the nameplate current rating of the generator.
Find the Answer
Answer: B
As noted in the first sentence of Sec. 445.13, the minimum ampacity shall not be less than 115% of the nameplate current rating of the generator, excluding the exception.