Where an orderly shutdown is required to minimize the hazard to personnel and equipment, a system of coordination based on which conditions is permitted?
A) coordinated short circuit protection
B) overload indication based on monitoring systems or devices
C) either A or B
D) both A and B
Find the Answer
Answer: D
As outlined in Sec. 240.12 of the 2014 NEC, where an orderly shutdown is required to minimize the hazard to personnel and equipment, a system of coordination is permitted based on a coordinated short circuit protection and overload indication based on monitoring systems or devices.