Moving Violations Video No. 183: Yet Another Lack of Support

Jan. 24, 2019
Russ reviews the rules on supporting liquidtight flexible non-metallic conduit.

This liquidtight flexible non-metallic conduit draped across this piece of equipment is definitely longer than 6 ft. This means it must be supported every 3 ft, as well as within 12 in. of that box. Since it isn’t, this is a violation of Sec. 356.30(1) of the 2017 NEC.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Xpress Elbows Guide for Industrial Construction

Learn how to get expedited elbows shipped within 2 days.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...