Stumped by the Code? NEC Rules for Mounting Equipment on Trees and Other Vegetation

April 18, 2018
Code Q&A | Mounting Equipment Trees

All questions and answers are based on the 2017 NEC.

Underlined text indicates a Code change.

Q. Does the NEC allow service equipment to be mounted on trees or other vegetation?

A. Trees or other vegetation aren’t permitted to be used for the support of overhead service conductor spans or service equipment [Sec. 230.10].

Service‑drop conductors installed by the electric utility must comply with the National Electrical Safety Code (NESC), not the National Electrical Code (NEC) [Sec. 90.2(B)(5)]. Overhead service conductors that aren’t under the exclusive control of the electric utility must be installed in accordance with the NEC.

Q. What wiring methods does the Code allow for service-entrance conductors?

A. Service-entrance conductors can be installed with any of the following wiring methods [Sec. 230.43]:

(1) Open wiring on insulators

(3) Rigid metal conduit (RMC)

(4) Intermediate metal conduit     (IMC)

(5) Electrical metallic tubing (EMT)

(6) Electrical nonmetallic tubing (ENT)

(7) Service-entrance cables

(8) Wireways

(9) Busways

(11) PVC conduit

(13) Type MC cable

(15) Flexible metal conduit (FMC) or liquidtight flexible metal conduit (LFMC) in lengths not longer than 6 ft

(16) Liquidtight flexible nonmetallic conduit (LFNC)

(17) High-density polyethylene conduit (HDPE)

(18) Nonmetallic underground conduit with conductors (NUCC)

(19) Reinforced thermosetting resin conduit (RTRC)

Q. What are the NEC requirements for service disconnects?

A. The service disconnect must open all ungrounded service-entrance conductors from the building premises wiring [Sec. 230.70].

(A) Location.

(1) Readily accessible. The service disconnecting means must be placed at a readily accessible location either outside the building or inside nearest the point of service conductor entry (see Figure).

WARNING: Because service-entrance conductors don’t have short-circuit or ground-fault protection, they must be limited in length when installed inside a building. Some local jurisdictions have a specific requirement as to the maximum length permitted within a building.

(2) Bathrooms. The service disconnect isn’t permitted to be installed in a bathroom.

(3) Remote control. If a remote-control device (such as a pushbutton for a shunt-trip breaker) is used to actuate the service disconnect, the service disconnect must be located at a readily accessible location either outside the building, or nearest the point of entrance of the service conductors as required by Sec. 230.70(A)(1).  

See the definition of “Remote Control” in Art. 100. The service disconnect must consist of a manually operated switch, a power-operated switch, or a circuit breaker that’s also capable of being operated manually [Sec. 230.76].

(B) Disconnect identification. Each service disconnecting means must be permanently marked to identify it as part of the service disconnecting means.  

(C) Suitable for use. Each service disconnect must be suitable for the prevailing conditions.

Q. What is the Code definition of a “tap conductor”?

A. The NEC defines a tap conductor as a conductor, other than a service conductor, that has overcurrent protection rated more than the ampacity of a conductor. See 240.21(A) and Sec. 240.21(B) for details [240.2].

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...