Ecmweb 22537 Nec Code Quandaries Oct 2018 Pr

Stumped by the Code? The Rules for Allowable Support Means of Boxes and Conduit Bodies

Oct. 17, 2018
NEC Code Quandaries

All questions and answers are based on the 2017 NEC.

Underlined text indicates a Code change.

Q. What are the Code rules for allowable support means of boxes and conduit bodies?

A. Boxes can be fastened to any surface that provides adequate support [Sec. 314.23(A)].

Boxes can be supported from any structural member, or they can be supported from grade by a metal, plastic, or wood brace [Sec. 314.23(B)].

Nails or screws used as a fastening means, must secure boxes by using outside brackets or by using mounting holes in the back or in a single side of the box, or pass through the interior within ¼ in. of the back or ends of the box. Screws aren’t permitted to pass through the box unless the exposed threads in the box are protected using approved means to avoid abrasion of conductor insulation. Mounting holes made in the field to support boxes must be approved by the authority having jurisdiction [Sec. 314.23(B)(1)].

Metal braces no less than 0.02 in. thick and wood braces not less than a nominal 1 in. × 2 in. can support a box [Sec. 314.23(B)(2)].

Boxes can be secured to a finished surface (drywall or plaster walls, or ceilings) by clamps, anchors, or fittings identified for the purpose [Sec. 314.23(C)].

Outlet boxes 100 cu in. or less can be supported to the structural or supporting elements of a suspended ceiling, if securely fastened by any of the following methods [Sec. 314.23(D)]:

(1) Ceiling‑Framing Members. An outlet box can be secured to suspended‑ceiling framing members by bolts, screws, rivets, clips, or other means identified for the suspended‑ceiling framing member(s). If framing members of suspended‑ceiling systems are used to support luminaires, they must be securely fastened to each other and must be securely attached to the building structure at appropriate intervals. In addition, luminaires must be attached to the suspended‑ceiling framing members with screws, bolts, rivets, or clips listed and identified for such use [Sec. 410.36(B)].

(2) Independent Support Wires. Outlet boxes can be secured with identified fittings to the ceiling‑support wires. If independent support wires are used for outlet box support, they must be taut and secured at both ends [Sec. 300.11(B)]. See Sec. 300.11(B) on the use of independent support wires to support raceways and cables.

(3) Raceway — Supported Boxes and Conduit Bodies Without Devices or Luminaires. Two intermediate metal or rigid metal conduits, threaded wrenchtight into the enclosure, can be used to support an outlet box that doesn’t contain a device or luminaire, if each raceway is supported within 36 in. of the box or within 18 in. of the box if all conduit entries are on the same side [Sec. 314.23(E)].

Exception: Conduit bodies are permitted to be supported by any of the following wiring methods:

 • Intermediate metal conduit, Type IMC


 • Rigid metal conduit, Type RMC

 • Rigid polyvinyl chloride conduit, Type PVC

 • Reinforced thermosetting resin conduit, Type RTRC

 • Electrical metallic tubing, Type EMT.

(4) Raceway — Boxes and Conduit Bodies with Devices or Luminaires. Two intermediate metal or rigid metal conduits, threaded wrenchtight into the enclosure, can be used to support an outlet box containing devices or luminaires, if each raceway is supported within 18 in. of the box [Sec. 314.23(F)] (see Figure).

Pendant Boxes containing a hub can be supported from a flexible cord connected to fittings that prevent tension from being transmitted to joints or terminals [Sec. 314.23(H)(1) and Sec. 400.10].        

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...