• Raceway Bonding Requirements

    Bonding requirements are outlined in Part V of Art. 250.
    Aug. 4, 2014

    Bonding jumpers for service raceways shall be used around impaired connections such as _____ .

    a) concentric knockouts
    b) eccentric knockouts
    c) reducing washers
    d) all of the above

    See answer and applicable Code reference

    The correct answer is: d) all of the above

    Bonding requirements are outlined in Part V of Art. 250. As noted in Sec. 250.92(B), "Bonding jumpers meeting the requirments of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s)."

    About the Author

    Mike Holt

    Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

    Sign up for EC&M Newsletters
    Get the latest news and updates.

    Voice Your Opinion!

    To join the conversation, and become an exclusive member of EC&M, create an account today!