Article 640 of the 2017 NEC provides different requirements for permanent installations of this equipment (Part II) than it does for installing portable versions (Part III). One of several places we can see that is in the requirements for flexible cords and cables [Sec. 640.21 and Sec. 640.42].
For flexible cords and cables between equipment and branch-circuit power, the requirements are identical [Sec. 640.21(A) and Sec. 640.42(A)]. But between loudspeakers and amplifiers or between loudspeakers:
- Permanent [Sec. 640.21(B)]: Cables must comply with Art. 725.
- Portable [Sec. 640.42(B)]: Cables must comply with Part I of Art. 400 and Parts I, II, and III of Art. 725. Cords and cables listed for portable use must be hard or extra-hard service per Art. 400.
The next subsection [Sec. 640.21(C) and Sec. 640.42(C)] has a similar difference in the requirements, and 640.21(C) is just for “between equipment” while 640.42(C) is for “between equipment and/or between equipment racks.”