    Q. In general, a disconnecting means is required for each sign and outline lighting system or feeder circuit and branch circuit supplying a sign or outline lighting system per 600.6. When is a disconnecting means not required per 600.6? When the sign ...
    April 13, 2007

    Q. In general, a disconnecting means is required for each sign and outline lighting system or feeder circuit and branch circuit supplying a sign or outline lighting system per 600.6. When is a disconnecting means not required per 600.6?

    1. When the sign is an exit directional sign supplied by batteries.
    2. When the sign is cord-connected with an attachment plug.
    3. When the sign is an exit directional sign located within a building.
    4. Both B and C.
    Answer: D

    Exception No. 1 and Exception No. 2 of 600.6 permit the disconnecting means to be omitted.