• Code Q&A: GFCIs in Unfinished Basements

    NEC rules for GFCIs in unfinished basements
    June 26, 2014

    Q. Is GFCI protection required for a sump pump installed in an unfinished basement of a dwelling unit?

    Find the Answer

    A. GFCI protection is required for all 15A and 20A, 125V receptacles located in the unfinished portion of a basement not intended as a habitable room and limited to storage and work areas [210.8(A)(5)].

    Exception: A receptacle supplying only a permanently installed fire alarm or burglar alarm system isn’t required to be GFCI protected [760.41(B) and 760.121(B)].

    Note: A receptacle outlet is required in each unfinished portion of a dwelling unit basement [210.52(G)].

    About the Author

    Mike Holt

    Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

    Voice your opinion!

    To join the conversation, and become an exclusive member of EC&M, create an account today!

    Sponsored Recommendations

    Sign up for EC&M Newsletters
    Get the latest news and updates.

    Latest from Q&A

    ID 379650282 © Yusnizam Yusof | Dreamstime.com
    dreamstime_xxl_379650282
    Test your knowledge of the NEC with this challenging question.
    ID 69201064 © Kiosea39 | Dreamstime.com
    dreamstime_xl_69201064
    Test your knowledge of the NEC with this challenging question.
    ID 376312510 © Евгений Полишко | Dreamstime.com
    dreamstime_xl_376312510
    Test your knowledge of the NEC with this challenging question.

    Sponsored