Q. What is the Code requirement in regard to installing single conductors outside of a raceway or cable?
Scroll Down to See the Answer
This answer is based on the 2017 NEC.
A. Single conductors must be installed within a Chapter 3 wiring method, such as a raceway, cable, or enclosure [300.3(A)]. They can also be installed in a cable tray when 1/0 AWG or larger [392.20(A)].
Overhead conductors can be installed in accordance with 225.6 [300.3(A) Ex].
These materials are provided to us by Mike Holt Enterprises of Leesburg, Fla. To view additional Code training materials offered by this company, visit www.mikeholt.com/code.About the Author

Mike Holt
Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.