• Code Quiz: Sizing EGCs

    NEC requirements for sizing equipment grounding conductors
    May 5, 2016

    When installing branch circuits for artificial bodies of water, such as municipal infrastructure, what is the minimum size (copper) equipment grounding conductor required for a 15A, 120V circuit?

    A) 14 AWG

    B) 12 AWG

    C) 10 AWG

    D) 8 AWG

    Find the Answer

    Answer: B

    Article 682 applies to the installation of electrical wiring for natural or artificially made bodies of water not covered by other Articles in the Code. Under normal circumstances, a 14 AWG (copper) equipment grounding conductor would be acceptable as per Sec. 250.122. However, as specifically noted in Sec. 682.31(A), the EGC shall not be smaller than 12 AWG.

    Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

    About the Author

    Steven Owen

    Sign up for EC&M Newsletters
    Get the latest news and updates.

    Voice Your Opinion!