Based on the 2023 NEC.
Question: How far past the front of a switchboard can the concrete pad extend?
See answer below.
Answer: 6 inches maximum.
Explanation: Section 110.26(A)(3) permits concrete pads under electrical equipment to extend no more than 6 in. past the front of the equipment.