Question: To comply with NEC requirements, a driven ground rod must have a resistance of ____ ohms or less.
- 10
- 20
- 25
- None of the above
See the answer below.
Answer: D
Explanation: Section 250.53 of the NEC requires that any made electrode that has a resistance greater that 25 ohms be supplemented by another electrode. The NEC does not require that an electrode have a resistance of 25 ohms or less, even after the addition of the supplemental electrode. It is worth noting though that many project specifications may have more restrictive requirements.