• Code Quiz: Supporting Conductors in Vertical Raceways

    Check your knowledge of the Code requirements regarding support for conductors in a raceway.
    March 28, 2019

    Question: What is the maximum length of a vertical run of conduit containing 500kcmil copper conductors that does not require supporting the individual conductors in the raceway?

    1. 10 ft
    2. 20 ft
    3. 30 ft
    4. 50 ft

    See the answer below.

    Answer: 50 ft

    Explanation: Section 300.19(A) requires support of conductors in vertical raceways if the vertical rise exceeds the values shown in Table 300.19(A). Additional intermediate supports are required to limit supported conductor lengths to not greater than those values specified in Table 300.19(A).

    Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].

    About the Author

    John Lupacchino

    Senior Design Engineer

    John began his career in electrical construction as an apprentice and worked his way through the trade. He is currently licensed in more than 80 jurisdictions. With more than 35 years of experience, he now plays a vital role in Gaylor Electric’s Engineering Department, where he serves as a senior design engineer. With a focus on design engineering, quality assurance, and code compliance, he has earned the highest level of respect from industry professionals alike. John currently serves as an alternate on NFPA 70 Code Making Panel No. 3. In addition, he enjoys sharing his electrical knowledge through education. As an Associated Builders and Contractors instructor, he continues to help grow a new generation of high-performing construction leaders.

    Sign up for EC&M Newsletters
    Get the latest news and updates.

    Voice Your Opinion!

    To join the conversation, and become an exclusive member of EC&M, create an account today!