Illinois Adopts 2018 International Energy Conservation Code

Feb. 27, 2019
Effective March 1, the updated code will increase energy efficiency and lower energy operating costs for commercial buildings.

Illinois has a new energy code, which means key changes are coming to those working in the lighting and electrical industry in the state. Effective March 1, 2019, the 2018 International Energy Conservation Code (IECC) becomes state law across Illinois.

Another change with the adoption is that state funded buildings now follow the 2018 IECC with ASHRAE/IESNA 90.1 as an alternative compliance path for a building owner and design team. Any building plans submitted on or after the effective date are expected to follow the new energy code requirements.

The updated code will increase energy efficiency and lower energy operating costs for commercial buildings.

Lighting control provisions changes include:

  • All occupancy sensor shutoff time delay is lowered to 20 min.
  • Open plan office areas are now required to use occupancy sensor controls for lighting shut off. Additionally, open plan office areas greater than 300 sq ft must limit the size of the occupancy sensor-controlled area to separate 600-sq-ft zones. General lighting in the individual zones must reduce power by at least 80% when occupants are not detected for 20 min. When all individual lighting zones within the open plan office area no longer detect any occupants, the entire office area must shut off all lighting.
  • A new code provision allows the use of Luminaire Level Lighting Control (LLLC) technologies as an alternate lighting control compliance option, as long as the luminaires have embedded occupancy sensors, daylight sensing controls, dimming, and wireless zoning capabilities.
  • An exception was added that allows a trade-off for daylighting controls. The exception requires an overall reduction of total building lighting power allowance equal to 40% of the allowed power for any daylight responsive zones receiving the exception.
  • Interior and exterior lighting power tables are revised to reduce the lighting power allowance for many applications. This supports the shift to more energy efficient lighting sources. Office building lighting power allowance is .79W/ft2, educational facility allowance is now .81W/ft2, and warehouse allowance is now .48W/ft2.

In addition, Illinois made one amendment to the 2018 IECC in the Electrical Power and Lighting Systems section (C405.1). The amendment establishes light efficacy requirements for dwelling units that do not follow the residential code. In these cases, no less than 90% of the light in these dwelling units shall have lamps with efficacy of 65 lm/W or more or light fixtures with efficacy of 55 lm/W or more.

Source: Legrand

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...