Circuit breakers operating at over 1kV, equipped with stored energy mechanisms, shall be designed to prevent the ________ of the stored energy unless the mechanism has been ______ charged.
A) build-up / electrically
B) release / fully
C) potential / manually
D) discharge / partially
See the answer below.
Answer: B
Section 490 of the 2017 NEC focuses on circuit breakers over 1,000V, nominal.
As specifically outlined in 490.45(A), “Circuit breakers equipped with stored energy mechanisms shall be designed to prevent the release of the stored energy unless the mechanism has been fully charged.”