Code Quiz: Space Required Above Cable Trays

Test your knowledge of the NEC with this challenging question.

Based on the 2026 NEC.

Question: How much space is required above cable trays to provide access for installing and maintaining cables?

See answer below.

 

 

 

 

Answer: 12 in.

Reference: Section 392.18(F)

Explanation: Section 392.18(F) now requires 12 in. above the tray for access, previously "sufficient space" was required but no measurement was given, leaving it open to interpretation. There are also four exceptions to the 12 in. requirement for specific installations.

Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected]

About the Author

John Lupacchino

Senior Design Engineer

John began his career in electrical construction as an apprentice and worked his way through the trade. He is currently licensed in more than 80 jurisdictions. With more than 35 years of experience, he now plays a vital role in Gaylor Electric’s Engineering Department, where he serves as a senior design engineer. With a focus on design engineering, quality assurance, and code compliance, he has earned the highest level of respect from industry professionals alike. John currently serves as an alternate on NFPA 70 Code Making Panel No. 3. In addition, he enjoys sharing his electrical knowledge through education. As an Associated Builders and Contractors instructor, he continues to help grow a new generation of high-performing construction leaders.

Sign up for our eNewsletters
Get the latest news and updates

Voice Your Opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!