Code Quiz: Branch Circuit Marking Requirements in an Operating Room

Test your knowledge of the NEC with this challenging question.
July 6, 2022

Based on the 2020 NEC.

Question: What are the marking requirements for isolated power system branch circuits in an operating room?

See answer below.

Answer:

Isolated Conductor No. 1 — Orange with at least one distinctive colored stripe other than white, green, or gray along the entire length of the conductor

Isolated Conductor No. 2 — Brown with at least one distinctive colored stripe other than white, green, or gray along the entire length of the conductor

Explanation: These requirements can be found in Sec. 517.160(A)(5) of the 2020 NEC.

Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].

About the Author

John Lupacchino

Senior Design Engineer

John began his career in electrical construction as an apprentice and worked his way through the trade. He is currently licensed in more than 80 jurisdictions. With more than 35 years of experience, he now plays a vital role in Gaylor Electric’s Engineering Department, where he serves as a senior design engineer. With a focus on design engineering, quality assurance, and code compliance, he has earned the highest level of respect from industry professionals alike. John currently serves as an alternate on NFPA 70 Code Making Panel No. 3. In addition, he enjoys sharing his electrical knowledge through education. As an Associated Builders and Contractors instructor, he continues to help grow a new generation of high-performing construction leaders.

Sign up for our eNewsletters
Get the latest news and updates

Voice Your Opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!